IEC 60890 Engineering Tool
Outdoor Anti-Condensation Heater Calculator
Calculate the exact PTC space heater wattage required to keep outdoor electrical enclosures above dew point based on enclosure dimensions, wall material thermal transfer, and mounting configuration.
1. Enclosure Parameters
Calculated Specification
Engineering Basis & IEC 60890 Formula
Steady-State Heater Formula
Required heating power is calculated as P_H = (k × Aₑ × ΔT) − Pᵥ, where Aₑ is the effective heat-dissipating surface area per IEC 60890 mounting coefficients, k is the enclosure wall heat-transfer coefficient (W/m²·K), and ΔT is the target temperature rise above ambient.
Maintaining internal air at least +5 K above outdoor ambient temperature keeps relative humidity below 65% RH, preventing dew-point condensation on inner roofs and terminal blocks.
Why Combine Heaters with Breathers & Sun Shields?
Daily 30 °C outdoor temperature swings generate ~10 kPa internal vacuum pulses inside sealed IP66 cabinets. Pairing a hygrostat-controlled PTC heater with an IP66/IP68 breather drain and an overhanging sun shield cuts both daytime solar heating and nighttime moisture suction.